TFM-04 FEL-A (2023 updated) Students also studied Science Engineering Mechanical Engineering Save TFM-04 FEL-A 83 terms lanerw16 Preview TFM04 281 terms coldcupofjoe Preview TFM03 Study Guide (NFPA 17A & NF ... 59 terms R3zource Preview TFMO4 134 term cold NFPA 11: Standard for __________. Low-, Medium-, and High-Expansion Foam 3 multiple choice options NFPA 12: Standard on __________. Carbon Dioxide Extinguishing Systems 3 multiple choice options NFPA 12a: Standard on __________. Halon 1301 Fire Extinguishing Systems 3 multiple choice options NFPA 15: Standard for __________. Water Spray Fixed Systems for Fire Protection 3 multiple choice options NFPA 16: Standard for __________. the Installation of Foam-Water Sprinkler and Foam-Water Spray Systems 3 multiple choice options NFPA 18: Standard on __________. Wetting Agents 3 multiple choice options NFPA 25: Standard for __________. the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems 3 multiple choice options NFPA 2001: Standard on __________. Clean Agent Fire Extinguishing Systems 3 multiple choice options AFFF stands for: Aqueous Film Forming Foam 3 multiple choice options

Read page 2 as text

Halon 1301 cylinders must be refilled/replaced if inspection shows ___________. 5% net weight loss, or 10% net pressure loss 3 multiple choice options Co2 cylinders must be refilled/replaced if at any time a net content loss of __________ or greater is found. 10% 3 multiple choice options A low-pressure Co2 cylinder may remain in service, even if it has a net content loss of 10% or greater, __________. only if it still meets minimum gas requirements 3 multiple choice options Halon 1301 cylinders must be weighed and the system must be inspected at least __________. Cylinder weight and pressure must be noted and the cylinder tagged. semi-annually 3 multiple choice options Enclosure for all systems besides Halon 1301 must be inspected __________. annually 3 multiple choice options Co2 operation condition must be inspected every __________. 30 days 3 multiple choice options High-pressure Co2 cylinders must be weighed at least __________. semi-annually 3 multiple choice options High-pressure Co2 cylinders shall not be recharged without a hydrostatic test if more than ___________ have elapsed from the date of the last test. 5 years 3 multiple choice options High-pressure cylinders may remain in service for up to __________ without a hydrostatic test, permitted they have not discharged and have remained in service the entire time. 12 years 3 multiple choice options System hoses and guages shall be tested every __________ and replaced if necessary. 5 years 3 multiple choice options System gauges must be recalibrated or replaced if test results are not accurate within _____ of the full scale. 3% 3 multiple choice options Low-pressure system hoses shall be tested at what PSI? 900 PSI 3 multiple choice options High-pressure system hoses shall be tested at what PSI? 2,500 PSI 3 multiple choice options In lieu of a hydrostatic test, every 5 years a Halon 1301 system can be visually inspected __________. as long as the system has remained in service the whole time 3 multiple choice options

That’s the free preview

You’ve read 2 of 6 pages. The whole document is yours with a free account, and it stays in your library.

Free

With a free account